Product Overview
The GT-SFD-Ex-IR series point-type infrared gas detector adopts imported infrared sensors and mature non-dispersive infrared (NDIR) technology to detect gases and vapors in the environment through spectral characteristics. It features high measurement accuracy, excellent stability and strong anti-interference capability. The sensor will not be poisoned and its detection performance is not affected by the oxygen content in the operating environment. With a wide linear detection range up to 0-100% VOL, it boasts a long maintenance cycle and a service life of more than 5 years.
Equipped with intelligent microprocessor processing technology, the device achieves accurate measurement and reliable alarm performance. The TFT version is fitted with a color screen, supporting Chinese menu operation and alarm log storage functions. An integrated on-site audible and visual alarm is available as an optional accessory.
Adopting a 3-wire working mode, the digital transmission module outputs high-quality 4~20mA industrial standard signals, which can be conveniently connected to data acquisition systems to realize remote real-time monitoring.
The detector housing is made of cast aluminum and stainless steel with superior corrosion resistance. Featuring an explosion-proof structure, it is suitable for continuous detection of flammable gas leakage and accumulation in various industrial environments.


Product Features
Adopts imported infrared sensors LCD display (Full-color TFT with Chinese menu), anti-glare interference Intelligent temperature compensation, fault indication & alarm Immune to poisoning, service life > 5 years SMT mounting technology guarantees stable operation Magnetic wand for configuration, calibration and other functions Product certified by national explosion-proof authority
Technical Parameters
| Item | Specification |
|---|---|
| Measurement Range | 0~100% LEL |
| Accuracy | 2% F.S |
| Repeatability | ±2% LEL |
| Long-term Stability | <±2% LEL |
| Sensor Installation | Resin encapsulated or plug-in type |
| Response Time | T90 < 10 s |
| Service Life | > 5 years |
| Sensor Poison Resistance | Resistant to H₂S poisoning |
| Explosion-proof Rating | Ex db IIC T6 Gb |
| Power Supply | 24V DC |
| Voltage Range | 18~30V DC; Power consumption < 1.5W |
| Output | 3-wire system + relay output + integrated sound-light alarm, or 485 output |
| HART Protocol | Meets HART protocol requirements |
| Housing Material | Cast aluminum + stainless steel |
| Electrical Interface | 3/4" NPT(F), G1/2" internal thread |
| Detectable Gas Types | Customizable upon request |
| Protection Rating | IP66 |
| Operating Temperature | -40°C ~ 80°C |
| Ambient Humidity | < 95% RH |
| Dimensions | 182 × 230 × 105 mm |
| Weight | Approx. 2 kg |